Accessing the connection compartment through the rear
352 NXAIR / ≤ 40 kA 110-0134.9 / 14
Contactor panels with panel width 435 mm only:
Remove the connecting elements from one of the vertical ledges (1):
• 15 bolts M8x20 with contact washers
Remove the vertical ledge, and store it together with the associated connecting elements.
Proceed in the same way with the other vertical ledge.
Fig. 651: Contactor panels with panel width 435 mm only:
30 bolts on ledges
Remove the sealing brackets (2) and store them.
Fig. 652: Contactor panels with panel width 435 mm only:
Removing the sealing brackets
Remove the connecting elements from the rear wall:
• 3 bolts M8x20 with contact washers (3)