Accessing the connection compartment through the rear
360 NXAIR / 40 kA 110-0134.9 / 14
Preconditions
If a withdrawable part / switching-device truck is present in the switching-device compartment:
High-voltage door closed
Withdrawable part / switching-device truck in test position
Feeder earthing switch in CLOSED position
Procedure
Verify that the position indicator of the feeder earthing switch on the high-voltage door shows
the vertical I position.
Fig. 660: Position indicator of feeder earthing switch on high-voltage door