Fitting the earthing device
372 NXAIR / ≤ 40 kA 110-0134.9 / 14
Impermissibly high voltage and current
Inappropriate use of the earthing device accessories will result in impermissibly
high voltage and current.
Use the earthing device exclusively for the maximum permissible short-
circuit current and the maximum permissible short-circuit duration.
Do not use the earthing device for short-circuit tests or purposes causing
similarly high voltages and currents.
Perform diligent inspection of the earthing device accessories before
each application.
Preconditions
• Withdrawable part / switching-device truck taken out of the panel
• Low-voltage connector stowed away
• Both shutter to the connection compartment and shutter to the busbar compartment closed
• Bushing contacts to be earthed isolated
• Earthing device accessories available and in perfect condition
• All panel versions except for contactor panels with 435 mm width:
Slip-on lever for opening the shutter available
• Padlock for shutter not to be used available
• Personal protective equipment put on
Upper shutter covering
bushing contacts linked
with busbar compartment
Lower shutter covering
bushing contacts linked with
connection compartment
Fig. 676: Fixed earthing point for
connecting the
earthing clamp