Fitting the earthing device
380 NXAIR / 40 kA 110-0134.9 / 14
Detach the earthing tulip from the bushing contact by pulling the earthing rod off.
Fig. 689: Detaching the earthing tulip
Fig. 690: Pulling earthing rod
Pull the tip with the tulip on it as far away as possible from the bushing contacts.
Pull the earthing tulip off the earthing rod and put it carefully on the panel base.
Fig. 691: Pulling off the tulip
To detach the other two earthing tulips, proceed in the same way.
Closing the shutter
DANGER
Electric shock
Close the shutter strictly as described in chapter 22 "Operating the
shutters" but leave the other shutter padlocked.
Close the shutter as described in chapter 22 "Operating the shutters".