Panels with motor operating mechanism control
392 NXAIR / 40 kA 110-0134.9 / 14
or
Fig. 710: Access mode indicator for racking: starting point "H" or "M"
Preconditions
Withdrawable circuit-breaker / circuit-breaker truck in test position
Panel set to local control
Control door open
Feeder earthing switch in OPEN position
Access mode indicator shows "M", or double-bit key for selecting racking mode inserted and access
mode indicator shows "H"
For electromagnetic interlock (optional):
Electromagnetic interlock deactivated
Procedure
If the access mode indicator shows “M” and the double-bit key is not inserted, insert it:
To release the actuating opening for the double-bit key, lift the operating slide (1) and hold it.
Insert the double-bit key (2).
Fig. 711: Lifting the operating slide and inserting the key: Starting point "M"