110-0134.9 / 14 NXAIR / 40 kA 93
If required, put the coupling pin of the feeder earthing switch operating shaft in vertical
position using the operating lever.
Fig. 154: Operating the feeder earthing switch operating shaft
Inserting the circuit-breaker truck in a panel
CAUTION
Maloperation
Protruding parts at the rear of the circuit-breaker truck can cause injuries.
Move and operate the circuit-breaker truck only at the front side.
NOTICE
Maloperation
The locking bracket at the circuit-breaker truck is exclusively designed for
interlocking the circuit-breaker truck with the switchgear frame.
As long as the circuit-breaker truck is not completely moved into the
panel, the locking indication at the locking bracket must show
UNLOCKED!
Operate the locking bracket only if the circuit-breaker truck has been
completely moved into the panel.
Do not push the locking bracket downwards towards LOCK if
the circuit-breaker truck is outside the panel.
the circuit-breaker truck is moved only partially into the panel.