Operating the circuit-breaker panel
96 NXAIR / 40 kA 110-0134.9 / 14
Locking the low-voltage connector
INFORMATION
In addition to these instructions, an instruction label on the circuit-breaker truck
informs about plugging on the low-voltage connector.
Follow the advice on the label (3) to push the longitudinal fastener.
Fig. 160: Instruction label on the circuit-breaker truck
Take the low-voltage connector out of the support located underneath the low-voltage
compartment.
Fig. 161: Low-voltage connector stowed
away
Fig. 162: Instruction label for the
low-voltage connector
Carefully plug on the low-voltage connector (2) from the front.
To secure the low-voltage connector, push the longitudinal fastener (1) of the coupling
downwards.
Fig. 163: Plugging on and securing the low-voltage connector
3