Description
National approvals NXPLUS C switchgear has obtained the following national approval:
GOST R certificate
Type approval NXPLUS C switchgear has been type-approved by the following classification societies:
Lloyds Register (LR)
Det Norske Veritas (DNV)
Germanischer Lloyd (GL)
Russian Maritime Register of Shipping (RMRS)
American Bureau of Shipping (ABS)
The switchgear is therefore also approved for application on ships and platforms.
Seismic withstand
capability (option)
NXPLUS C switchgear can be upgraded for regions at risk from earthquakes. For upgrading,
earthquake qualification testing has been carried out in accordance with the following
standards:
IEC 60068-3-3 “Guidance – seismic test methods for equipment”
IEC 60068-2-57 “Test Ff: Vibration – Time-history method”
IEC 60068-2-59 “Test Fe: Vibration – Sine-beat method”
IEEE 693-2005 “Recommended Practice for Seismic Design of Substations.
For installation on even and rigid concrete or steel structure (without considering building
influences), the tested ground accelerations meet the following requirements:
Uniform Building Code 1997 (UBC) – Zone 4
California Building Code 1998 (CBC) – Zone 4
IEEE 693-2005 – High required response spectrum.