10/293 Revision 11 • INSTALLATION AND OPERATING INSTRUCTIONS • NXPLUS C • 802-9081.9
Description
6 Features
Technology Factory-assembled, type-tested and metal-enclosed switchgear for indoor installation
Stainless-steel vessel welded gas-tight
Gas-insulated switching-device compartment
Cable connection and busbar, single-pole insulated
Installation and extension of the switchgear possible without SF
6
gas work
Screened busbar, silicone-rubber insulated
Cable connection from front with cable plugs
Maintenance-free under normal operating conditions
Insulating gas SF
6
Sulfur hexafluoride SF
6
is used as insulating gas. SF
6
insulates live parts between each other
and against the vessel wall. For panels with switch disconnector, SF
6
serves also for
extinguishing the internal arc.
The switchgear is delivered ex works with SF
6
filling, ready for service. The SF
6
filling is
provided to last the total service life of the switchgear.
No gas work is required for installation on site and later extensions.
Filling quantity as per rating plate.
Personal safety Safe-to-touch due to metal enclosure of live parts
Clear mimic diagram with mechanical position indicators
HV HRC fuses are only accessible when outgoing feeders are earthed
Logical mechanical interlocking
Capacitive voltage detecting system to verify safe isolation from supply
Earthing of outgoing feeders by means of make-proof earthing switch (this does not apply
to disconnector panels)
Resistance to internal arcing
- Pressure-resistant design of connection compartments
- Rear pressure relief duct (optional for wall-standing arrangement)
Security of operation and
availability
Hermetically sealed primary enclosure independent of environmental effects, such as
pollution, humidity and small animals
Welded switchgear vessel, sealed for life
Operating mechanisms of switching devices accessible outside the switchgear vessel
Maloperation is practically excluded due to interlocks and logical arrangement of operating
elements
Self-monitoring ready-for-service indicator, easy to read, independent of temperature and
environmental pressure variations, with contactless measured-value acquisition and with
signaling switch (option) 1 changeover contact for telecommunication
Minimum fire load
Switchgear vessel designed as "sealed pressure system" according to IEC 62271-200, i.e. the
insulating gas filling requires no maintenance
Cost-efficiency Extremely low "lifecycle costs" and maximum availability thanks to:
Maintenance-free design under normal operating conditions (for the service life)
Minimum space requirement
Long service life

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens NXPLUS C and is the answer not in the manual?

Siemens NXPLUS C Specifications

General IconGeneral
Rated voltageUp to 24 kV
Rated frequency50/60 Hz
Protection degreeIP4X
Insulation mediumSF6
StandardsIEC 62271-200
Operating mechanismSpring-operated