EasyManua.ls Logo

Siemens NXPLUS C - HV HRC Fuse Assembly

Siemens NXPLUS C
293 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Description
32/293 Revision 11 • INSTALLATION AND OPERATING INSTRUCTIONS • NXPLUS C • 802-9081.9
Cable-type current transformer
- Inside diameter of transformer 56 mm
- Max. usable height 170 mm
Electrical data of current transformer type 4MC
9.8 HV HRC fuse assembly
Features With fuse slide for fuse replacement without tools
HV HRC fuse-links according to DIN 43625 (main dimensions) with striker in "medium"
version according to IEC 60282-1
- as short-circuit protection before transformers or motors,
- with selectivity to upstream and downstream connected equipment,
- 1-pole insulated
Reference dimension e of the fuse-links
- Ur = 12 kV: e = 292 mm (option e = 442 mm)
- Ur = 24 kV: e = 442 mm
Requirements according to IEC 62271-105 / VDE 0671-105 met for HV HRC fuse-links in
combination with the three-position switch-disconnector
Thermal striker tripping when the corresponding HV HRC fuse-link is used
Climate-independent and maintenance-free, with fuse boxes made of cast resin
Arrangement of the HV HRC fuse assembly underneath the switching-device vessel
HV HRC fuse assembly connected to the three-position switch-disconnector / vacuum
contactor via welded-in bushings and connecting bars
Operating voltage max. 0.8 kV
Rated short-duration power- frequency withstand
voltage (winding test)
3 kV
Rated frequency 50/60 Hz
Rated continuous thermal current 1.0 / 1.2 / 1.33 / 1.5 / 2.0 x rated current (primary)
Rated short-time thermal current, max. 3 s 31.5 kA
Rated current dynamic unlimited
primary 40 A to 2500 A
secondary 1 A and 5 A
Multiratio (secondary) 200 - 100 A to 2500 - 1250 A
Core data dependent on rated primary current max. 3 cores
Measuring core Rating 2.5 VA to 30 VA
Class 0.2; 0.5; 1
Overcurrent
factor
FS5, FS10
Protection core Rating 2.5 VA to 30 VA
Class 5P or 10P
Overcurrent
factor
10 to 30
Permissible ambient air temperature max. 60 °C
Insulation class E
Bushing
Switchgear vessel
Sealing cover with seal
Tripping pin for spring-operated/
stored-energy mechanism
Striker of the HV HRC fuse-link
and articulation for tripping the
spring-operated/stored-energy
mechanism
HV HRC fuse-link
Fuse box

Table of Contents

Related product manuals