Installation
158/293 Revision 11 • INSTALLATION AND OPERATING INSTRUCTIONS • NXPLUS C • 802-9081.9
âž Screw nut-and-washer assemblies onto the studs.
Fig. 115: Example for panel width 600 mm
16.2 Connecting cable T-plugs
For NXPLUS C switchgear, only cable T-plugs shielded by means of an external semi-
conductive layer may be used as a rule. The suitable cable plugs for outside-cone bushings of
interface type C according to EN 50181 are listed in the section "Description" (see page 34,
"Cable connection"NXPLUS C).
Please select the tightening torque of the bolted joint "cable T-plug - bushing" according to the
specifications of the respective cable T-plug manufacturer.
If there are no specifications from the cable T-plug manufacturer's side, please tighten the
bolted joint with 50 Nm.
Phase sequence
Fig. 116: Phase sequence of bushings in the cable compartment
Preparations âž Earth the feeder.
âž Undo the fixing bolts of the cable compartment cover.
âž Lift the cable compartment cover and remove it to the front.
âž Remove the floor cover (see page 155, "Removing the floor cover").
âž Cut rubber sleeves to size (see page 156, "Cutting the rubber sleeves to size").
Mounting cable T-plugs
on cable ends
DANGER
Life-endangering high voltage
Will cause death, serious injury or considerable property damage.
Do not energize the switchgear as long as no cables or surge-proof caps are mounted.
âž If the panel has to be live without connected cables, close the outside-cone bushings in a
surge-proof way.
âž Mount surge-proof caps onto bushings type C (with bolted contact M16).