Service information
278/293 Revision 11 • INSTALLATION AND OPERATING INSTRUCTIONS • NXPLUS C • 802-9081.9
Fig. 183: Fuse tripping
29.3 Visual check of slow motion mechanism
Refers to panel types:
Circuit-breaker panel (panel width 900 mm)
Bus sectionalizer (panel width 900 mm)
Disconnector panel (panel width 900 mm)
Circuit-breaker panel with increased number of 30000 operating cycles (panel width
600 mm)
Slow motion mechanism Check smooth operation of the interrogation lever .
Check firm seating of all terminal connections .
Check smooth operation of the control gate .
Fig. 184: Slow motion mechanism