802-9081.9 • INSTALLATION AND OPERATING INSTRUCTIONS • NXPLUS C • Revision 11 97/293
Installation
In a weatherproof place
Protected against damage
If packed in seaworthy crates, the switchgear can be stored for a maximum of 6 months
(desiccant bags)
Store transport units in such a way that they can be taken out later in the correct order for
installation
Switchgear storage in
closed rooms
Store the switchgear in a closed room. The storage room must have the following
characteristics:
Floor with adequate load-bearing capacity (weights as per delivery note)
Even floor to enable stable storage.
Well-ventilated and as free of dust as possible
Dry and protected against humidity and vermin (e.g. insects, mice, rats)
Heatable up to at least 2 °C above outside temperature to prevent condensation.
Check humidity in the packings every 4 weeks (condensation)
Do not unpack small parts to avoid corrosion and loss.
Outdoor storage of
switchgear packed in
seaworthy crates
If the switchgear or parts thereof are delivered in seaworthy crates, the crates can be stored up
to 6 months in other rooms or outdoors. The storage place must have the following
characteristics:
Floor with adequate load-bearing capacity (weights as per delivery note)
Roofed, protected against humidity (rain water, flooding, melting water from snow and ice),
pollution, vermin (rats, mice, termites, etc.) and unauthorized access
For protection against floor humidity, place all crates on planks and square timber.
After 6 months of storage, have the desiccant agent regenerated professionally. To do this,
ask for expert personnel via the regional Siemens representative
13.3 Tools/auxiliary means
Before starting to work on the switchgear, provide for the tools/auxiliary means required:
Hexagonal screwdriver insert (min. length 140 mm) for hexagon socket-head bolt 10 mm
DIN 7422
Torx screwdriver Tx25
Torque wrench 20 - 50 Nm
Ratchet, reconnectable DIN 3122
Extension DIN 3123 40 - 125
Socket spanner inserts DIN 3124, socket spanner inserts size 17, 18 and 19, min. length
80 mm
Water level
Lifting truck
Reinforcing bars, roller crowbars
Transport rollers, tubes
Lifting rods, length 753 mm, Ø 20 mm, e.g. certified lifting rods (order number 802-9047.3,
to be procured from the regional Siemens representative)
Lifting rods, length 1053 mm, Ø 20 mm, e.g. certified lifting rods (order number 804-
0011.3, to be procured from the regional Siemens representative)
Technical requirements for lifting rods:
- Diameter: 20 mm
- Loading capability (yield strength): R
e
780 MPa (N/mm
2
)
Lint-free cleaning paper
Wiping cloths
Grinding sponge with corundum grit 100
Abrasive fabric

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens NXPLUS C and is the answer not in the manual?

Siemens NXPLUS C Specifications

General IconGeneral
BrandSiemens
ModelNXPLUS C
CategoryCircuit breakers
LanguageEnglish

Related product manuals