230/293 Revision 11 • INSTALLATION AND OPERATING INSTRUCTIONS • NXPLUS C • 802-9081.9
26.4 Operating switch-disconnector, disconnector, ring-main and metering
panels with 600 mm panel width
Switch-disconnector, disconnector, ring-main or metering panels: Connecting the
feeder to the busbar
1
Initial situation
2
Push the interrogation lever
downwards.
3
Push the control gate to the left.
4
Switch the three-position switch-
disconnector to CLOSED position (insert the
operating lever and turn 90° clockwise).
5
Remove the operating lever (the
interrogation lever and the control gate
return to their initial position).