EasyManuals Logo

Siemens NXPLUS C User Manual

Siemens NXPLUS C
293 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #228 background imageLoading...
Page #228 background image
Operation
228/293 Revision 11 • INSTALLATION AND OPERATING INSTRUCTIONS • NXPLUS C • 802-9081.9
Vacuum contactor panel: Earthing the feeder
1
Initial situation
2
Push the interrogation lever downwards
and hold it.
3
Push the control gate to the right (the
interrogation lever locks in lower position.
The actuating opening for the EARTHING
function opens).
4
Switch the three-position switch-
disconnector to EARTHED position (insert
the operating lever and turn 90° clockwise).
5
Remove the operating lever (the
interrogation lever and the control gate
return to their initial position. The actuating
opening closes).

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens NXPLUS C and is the answer not in the manual?

Siemens NXPLUS C Specifications

General IconGeneral
Rated voltageUp to 24 kV
Rated frequency50/60 Hz
Protection degreeIP4X
Insulation mediumSF6
StandardsIEC 62271-200
Operating mechanismSpring-operated

Related product manuals