Operation
Bus sectionalizer panel with one three-position disconnector: De-earthing the right-
hand busbar system
1
Initial situation
2
Remove the padlock (the locking device
goes down).
3
To de-earth the busbar system, open the
circuit-breaker.
4
Push the interrogation lever downwards and
hold it.
5
Push the control gate to the right and hold it
(the interrogation lever locks in lower
position. The actuating opening for the
READY-TO-EARTH function opens).
6
Switch the three-position disconnector from
READY-TO-EARTH to OPEN position (insert
the operating lever and turn 180° counter-
clockwise).
7
Remove the operating lever (the
interrogation lever and the control gate
return to their initial position).