Service information
274/293 Revision 11 • INSTALLATION AND OPERATING INSTRUCTIONS • NXPLUS C • 802-9081.9
Checking the interlocking conditions
Put the switchgear panel into operation according to the installation and operating
instructions.
The maintenance of the operating mechanism is completed.
Switch positions of the three-
position disconnector
Switch position of
the circuit-breaker
Interlocking condition
DISCONNE
CTING
function
READY-TO-EARTH
function
OPEN OPEN OPEN
"Feeder" locking device cannot be operated.
Cable compartment cover cannot be removed.
"Three-position disconnector" switching operation can be selected; operating lever for
the DISCONNECTING or READY-TO-EARTH operation can be inserted; three-position
disconnector can be operated.
Circuit-breaker can be operated.
OPEN OPEN CLOSED
"Feeder" locking device cannot be operated.
Cable compartment cover cannot be removed.
CLOSED --- OPEN
Operating lever for READY-TO-EARTH operation cannot be inserted.
Circuit-breaker can be operated.
CLOSED --- CLOSED
"Feeder" locking device cannot be operated.
Cable compartment cover cannot be removed.
"Three-position disconnector" switching operation cannot be selected.
Circuit-breaker can be operated.
--- CLOSED CLOSED
"Three-position disconnector" switching operation cannot be selected.
"Feeder" locking device can be operated.
Cable compartment cover can be removed.
Circuit-breaker can be operated.
--- CLOSED OPEN
Operating lever for DISCONNECTING operation cannot be inserted.
"Feeder" locking device cannot be operated.
Cable compartment cover cannot be removed.
Circuit-breaker can be operated.

Table of Contents