48/293 Revision 11 • INSTALLATION AND OPERATING INSTRUCTIONS • NXPLUS C • 802-9081.9
Installation possibilities for paper-insulated non-draining cables
Installation possibilities for paper-insulated mass-impregnated cables
Circuit-breaker panel 630 A, 1000 A Switch-disconnector panel 630 A Disconnector panel 1000 A Ring-main panel 630 A Vacuum
contactor panel Circuit-breaker panel 1250 A
1
Disconnector panel 1250 A
1
1
At a continuous current of more than 1150 A, cable sealing ends with tin-plated, nickel-plated or silver-plated cable lugs are required.
Make Conductor
cross-
section
2
2
Observe the actual current- and short-circuit-carrying capacity of the cables and sealing ends.
Insulation
Cable T-plugs Coupling inserts/coupling
plugs
Distribution kit
for three-core
cables
Surge arresters According to
standard
[mm
2
] bolted bolted additionally
GOST
(Russia, CIS)
GB/DL (China)
12 kV 12 kV
1 cable per panel and phase
Nexans
Euromold
35…300 EPDM 1x 430TB/G
-
1x distribution
kit MIND
300SA-5(10)SA IEC, GOST, GB/DL
nkt cables 25…120 Silicon
e
1x SÜEV10-120CU-xxxx-
CB24
- -
CSA 12-x IEC, GOST, GB/DL
150…240 Silicon
e
1x SÜEV10-240CU-xxxx-
CB24
- -
CSA 12-x IEC, GOST, GB/DL
2 cables per panel and phase
Nexans
Euromold
35…300 EPDM 1x 430TB/G 1x 300PB/G 2x distribution
kit MIND
-
IEC, GOST, GB/DL
nkt cables 25…120 Silicon
e
1x SÜEV10-120CU-xxxx-
CB24
1x SÜEV10-120CU-xxxx-
CC24
-
CSA 12-x IEC, GOST, GB/DL
150…240 Silicon
e
1x SÜEV10-240CU-xxxx-
CB24
1x SÜEV10-240CU-xxxx-
CC24
-
CSA 12-x IEC, GOST, GB/DL
3 cables per panel and phase
Nexans
Euromold
35…300 EPDM 1x 430TB/G 2x 300PB/G 3x distribution
kit MIND
-
IEC, GOST, GB/DL
Circuit-breaker panel 630 A, 1000 A Switch-disconnector panel 630 A Disconnector panel 1000 A Ring-main panel 630 A Vacuum
contactor panel Circuit-breaker panel 1250 A
1
Disconnector panel 1250 A
1
1
At a continuous current of more than 1150 A, cable sealing ends with tin-plated, nickel-plated or silver-plated cable lugs are required.
Make Conductor
cross-
section
2
2
Observe the actual current- and short-circuit-carrying capacity of the cables and sealing ends.
Insulation
Cable T-plugs Coupling inserts/
coupling plugs
Distribution kit
for three-core
cables
Surge arresters According to
standard
[mm
2
] bolted bolted
GOST
(Russia, CIS)
GB/DL (China)
12 kV 12 kV
1 cable per panel and phase
nkt cables 25…120 Silicone 1x SÜEV10-120CU-
xxxx-CB24
- - CSA 12-x IEC, GOST, GB/DL
150…240 Silicone 1x SÜEV10-240CU-
xxxx-CB24
- - CSA 12-x IEC, GOST, GB/DL
2 cables per panel and phase
nkt cables 25…120 Silicone 1x SÜEV10-120CU-
xxxx-CB24
1x SÜEV10-120CU-
xxxx-CC24
- CSA 12-x IEC, GOST, GB/DL
150…240 Silicone 1x SÜEV10-240CU-
xxxx-CB24
1x SÜEV10-240CU-
xxxx-CC24
- CSA 12-x IEC, GOST, GB/DL