Landis & Staefa Division CC1B7865E February 10, 2000 43/56
8. Configuration
The switching point is independent of the controller setpoint; only the limit value «
AL»
determines the switching point.
Function: relay is active when measured value > limit value.
Example:
AL
= 50,
HYSt
= 2
Measured value rising: relay «K6» switches on at 51 °C.
Measured value falling: relay «K6» switches off at 49 °C.
AL
HYSt
Measured value
7865d07e/0300
Output 4
As for lk7, but with inverted switching function.
AL
HYSt
Measured value
7865d08e/0300
Output 4
HYSt
= switching differential
AL
= limit value
Ö
Chapter 7 «Parameter settings»
Function Ik7
Function Ik8