EasyManua.ls Logo

Siemens S7-300 - Technical Data - SM 326; DI 24 X DC 24 V

Siemens S7-300
356 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Digital modules
8.3 SM 326; DI 24 x DC 24V
Fail-safe signal modules
102 Installation and Operating Manual, 01/2010, A5E00085586-10
8.3.10 Technical data - SM 326; DI 24 x DC 24V
Overview
Technical data
Dimensions and Weight
Dimensions W x H x D (mm) 80 x 125 x 120
Weight Approx. 442 g
Module-Specific Specifications
Configuration in Run (CiR) supported Yes (only in standard mode)
Behavior of non-configured inputs during CiR
Return the process value that was valid prior to
parameter assignment
Supports time stamping Yes
Accuracy
20 ms to 30 ms
Number of inputs
Single-channel
24
Dual-channel
12
Assigned address area
In the I/O input area
10 bytes
In the I/O output area
4 bytes
Cable length
Unshielded
100 m, maximum
Shielded
200 m, maximum
Front connectors 40-pin
Maximum achievable Safety Integrity Level in safety mode
According to IEC 61508
SIL 3
According to EN 954-1
Category 4
According to ISO 13849:2006
PLe
Fail-safe performance characteristics SIL 2 SIL 3
low demand mode (average probability of
failure on demand)
< 1.00E-04 < 1.00E-05
high demand / continuous mode (probability
of a dangerous failure per hour)
< 1.00E-08 < 1.00E-09
Voltages, Currents, Potentials
Rated supply voltage of the electronic system
and sensors 1L+, 2L+
24 V DC
Reverse polarity protection
Yes
Power failure ride-through (does not apply to
sensor supply outputs)
5 ms