Digital modules   
8.3 SM 326; DI 24 x DC 24V 
  Fail-safe signal modules 
102  Installation and Operating Manual, 01/2010, A5E00085586-10 
8.3.10  Technical data - SM 326; DI 24 x DC 24V 
Overview  
 
Technical data 
Dimensions and Weight 
Dimensions W x H x D (mm)  80 x 125 x 120 
Weight  Approx. 442 g 
Module-Specific Specifications 
Configuration in Run (CiR) supported  Yes (only in standard mode) 
  Behavior of non-configured inputs during CiR 
Return the process value that was valid prior to 
parameter assignment 
Supports time stamping  Yes 
  Accuracy 
20 ms to 30 ms 
Number of inputs 
  Single-channel 
24 
  Dual-channel 
12 
Assigned address area  
  In the I/O input area 
10 bytes 
  In the I/O output area 
4 bytes 
Cable length 
  Unshielded 
100 m, maximum 
  Shielded 
200 m, maximum 
Front connectors  40-pin 
Maximum achievable Safety Integrity Level in safety mode 
  According to IEC 61508 
SIL 3 
  According to EN 954-1 
Category 4 
  According to ISO 13849:2006 
PLe 
Fail-safe performance characteristics  SIL 2  SIL 3 
  low demand mode (average probability of 
failure on demand) 
< 1.00E-04  < 1.00E-05 
  high demand / continuous mode (probability 
of a dangerous failure per hour) 
< 1.00E-08  < 1.00E-09 
Voltages, Currents, Potentials 
Rated supply voltage of the electronic system 
and sensors 1L+, 2L+ 
24 V DC 
  Reverse polarity protection 
Yes 
  Power failure ride-through (does not apply to 
sensor supply outputs) 
5 ms