Digital modules
8.7 SM 326; F-DO 10 x DC 24V/2A PP (6ES7326-2BF10-0AB0)
Fail-safe signal modules
Installation and Operating Manual, 01/2010, A5E00085586-10
165
8.7.2 SM 326; F-DO 10 x DC 24V/2A PP applications
Selecting the application
The figure below helps you to select an application based on availability and fail-safe
operation requirements. The next pages provide information on the module wiring for a
specific application, and on the parameters to set in
STEP 7
using the
S7 Distributed Safety
or
S7 F Systems
optional package.
0RGXOH
UHGXQGDQW"
6,/&DW3/H
6DIHW\PRGH
6,/&DW3/H
6DIHW\PRGH
KLJKDYDLODELOLW\
1R
<HV
$SSOLFDWLRQVWR
Figure 8-54 Application Selection - SM 326; F-DO 10 x DC 24V/2A PP
Test pulses of the light and dark test
PV
V
0RGXOHF\FOH
$VVLJQHGPD[WHVWWLPH
PD[RUVHFRQGV
SURJUDPPDEOHPD[OLJKWWHVWWLPHRUWHVWDWRXWSXWVLJQDO
,QWHUYDOORDGGHSHQGHQW
W
1
Figure 8-55 Light test, if assigned
The typical break between two test pulses is 0.5 seconds. There can be another test pulse
in between. The gap between the first test pulse and the additional test pulse is one
module cycle.