8.4.1 Properties, front view, wiring diagram and block diagram
Order number
6ES7326-1RF00-0AB0
Properties
SM 326; DI 8 x NAMUR has the following properties:
SIMATIC S7-Ex digital module
suitable for connecting signals from the Ex area
8 single-channel inputs or 4 two-channel inputs, electrically isolated
Rated input voltage 24 V DC
Suitable for the following sensors
In accordance with DIN 19234 and NAMUR (with diagnostic evaluation)
connected mechanical contacts (with diagnostic evaluation)
8 short-circuit-proof sensor supplies, each to one channel, electrically isolated
Group fault display (SF)
Safety mode display (SAFE)
Status display for each channel (green LED)
Programmable diagnostics functions
Assignable diagnostic interrupt
Supports operation in standard and safety mode
Note
The fail-safe performance characteristics in the technical data apply to a proof-test interval of
10 years and a mean time to repair of 100 hours.
Compliance with air gaps and creepage distances in the Hazardous Area
Note
For the digital input module SM 326; DI 8 x NAMUR, supply of L+ / M to maintain air gaps
and creepage distances in the potentially explosive atmosphere in the Hazardous Area has
to take place via the cable guide (order no. 6ES7393-4AA10-0AA0) (see chapter "Special
Features
when Wiring SM 326; DI 8 x NAMUR for Haz
ardous Areas (Page 109)").

Table of Contents