Digital modules
8.3 SM 326; DI 24 x DC 24V
Fail-safe signal modules
82 Installation and Operating Manual, 01/2010, A5E00085586-10
8.3.2 Use cases for the SM 326; DI 24 24V DC
Selecting the application
The figure below helps you to select an application based on availability and fail-safe
operation requirements. The next pages provide information on the module wiring for a
specific application, and on the parameters to set in
STEP 7
using the
S7 Distributed Safety
or
S7 F Systems
optional package.
 
0RGXOH
UHGXQGDQW"
6WDQGDUGPRGH 6DIHW\PRGH
6DIHW\PRGH"
5HTXLUHG
VDIHW\FODVV"
0RGXOH
UHGXQGDQW"
0RGXOH
UHGXQGDQW"
6WDQGDUG
PRGH
6WDQGDUG
PRGHKLJK
$YDLODELOLW\
6,/
6DIHW\
PRGH
6,/
6DIHW\PRGH
KLJKDYDLODELOLW\
6,/
6DIHW\PRGH
6,/
6DIHW\PRGH
KLJKDYDLODELOLW\
$SSOLFDWLRQVWR
1R
1R1R1R
<HV <HV <HV
<HV
6,/
&DW3/H
6,/
&DW3/G
Figure 8-6 SM 326; DI 24 x DC 24V - Selecting an application
WARNING
The maximum Safety Integrity Level is determined by the sensor quality and the length of
the proof-test interval to IEC 61508. Always wire sensors whose quality does not meet
Safety Integrity Level requirements redundantly to two channels.
Note
You can define 1oo1 and 1oo2 sensor evaluation for a module (for example, see table
SM
326; DI 24 x DC 24V: Example of channel configuration
in the chapter
Properties, front View,
wiring diagram and block diagram
).