Analog modules
9.3 SM 336; F-AI 6 x 0/4 ... 20 mA HART
Fail-safe signal modules
Installation and Operating Manual, 01/2010, A5E00085586-10
289
9.3.17.3 HART communication records
Transfer data records
HART communication can be controlled by one client per channel. Each channel has a
separate transfer area available. Each transfer area consists of the command and reply data
records.
Coordination rules for HART communication
Fixed data record numbers are assigned to each client/channel:
Channel Client Data record
0 Command 80
0 Reply 81
1 Command 82
1 Reply 83
2 Command 84
2 Reply 85
3 Command 86
3 Reply 87
4 Command 88
4 Reply 89
5 Command 90
5 Reply 91
After writing a command data record, a client has to read the reply data record before
writing another command data record.
From master class 2 (e. g.
SIMATIC PDM
or the engineering system with PROFIBUS
master), the client can evaluate the "processing status" in the reply data record: If the
processing status is "successful" or "faulty", the data record contains current reply data or
error displays.
The data record must always be read in its entirety, since after it is first read with a
successful or faulty status, the data record can be changed by the module.
The status component in the reply data record (= HART status bytes) provides
information on whether and which errors have occurred.