Fault reaction and diagnostics 
  6.1 Fault reactions of the F-SMs 
Fail-safe signal modules 
Installation and Operating Manual, 01/2010, A5E00085586-10 
55 
6.1.3  Fault reactions in safety mode with parameter setting "Keep last valid value" 
Applications  
Typical applications for safety mode with parameter setting "Keep last valid value" are: 
●  Ventilation systems 
●  Smoke flaps 
Fault reactions  
 
 
Note 
Consult the respective standards for installation. 
 
NOTICE 
 
Only standards EN54-2 /-4 or NFPA72 will be met with parameter setting "Keep last valid 
value". 
The last valid value will be retained in case of the following communication 
errors/interruptions: 
  STOP of F-CPU (interruption of PROFIsafe communication) 
  Interruption of PROFIsafe communication 
–  in case of CRC errors 
–  Interruption of PROFIBUS/PROFINET connection 
–  Timeout of data frame monitoring 
  Error in safety program of the F-CPU 
  Error in PROFIsafe protocol 
The current process value will be issued again once PROFIsafe communication resumes. 
The safe status "0" will be assumed at the digital output module in case of the following 
errors: 
  Channel errors (independent of parameter "Behavior after channel faults") 
  Module faults 
With a pending channel fault in connection with 
S7 Distributed Safety
, the last valid value of 
all error-free channels will be retained after a STOP-RUN transition of the F-CPU until 
reintegration. You will have to correct the channel fault before reintegration if the parameter 
"Behavior after channel fault" is set to "Passivate the entire module". 
 
To increase availability use application 6 of the SM 326; F-DO 10 x DC 24V/2A PP.