Digital modules
8.7 SM 326; F-DO 10 x DC 24V/2A PP (6ES7326-2BF10-0AB0)
Fail-safe signal modules
Installation and Operating Manual, 01/2010, A5E00085586-10
173
Assignable parameters for application 6
Table 8- 24 Parameters for application 6 of SM 326; F-DO 10 x 24V/2A PP
Parameters Range of values Type Effective
range
"Parameters" tab
Mode of operation Safety mode Static Module
F_Monitoring_Time (ms) 10 ms to 10000 ms Static Module
Diagnostic interrupt Activated/deactivated Static Module
Fail-safe value
Switch to fail-safe value
Keep last valid value
Static Module
Maximum test period 100 / 1000 s Static Module
Load voltage failure diagnostics Activated/deactivated Static Channel
group
Activated Activated/deactivated Static Channel
Diagnostics: Wire break Activated/deactivated Static Channel
Activated light test Activated/deactivated Static Channel
Max. time for light test (ms) 0.6 ms to 5 ms Static Channel
Max. read-back time for dark test
(ms)
0.6 ms to 400 ms Static Channel
Redundant switched
Activated
Static Channel
8.7.7 Diagnostic messages SM 326; F-DO 10 x DC 24V/2A PP
Diagnostics using the LED display
The F-SM indicates faults by means of its SF LED (group fault LED). The SF LED is
activated when the F-SM generates a diagnostic message.
The SF LED flashes as long as a cleared fault has not been acknowledged. It goes dark
when all faults have been eliminated and acknowledged.
The SF LED flashes until you acknowledge passivation following a module fault.