Analog modules
9.3 SM 336; F-AI 6 x 0/4 ... 20 mA HART
Fail-safe signal modules
268 Installation and Operating Manual, 01/2010, A5E00085586-10
9.3.15 Parameters of analog input module F-AI 6 x 0/4 ... 20mA HART
Table 9- 26 Parameters of module SM 331; F-AI 6 x 0/4...20mA HART
Parameters Range of values Default Parameter
type
Effective
range
F-parameters
F_Source_Address Dependent on the F-CPU
used
F_destination_address 1 to 1022
DIP switch position
(9........0)
0000000001 To
1111111110
F_Monitoring_Time (ms) 1 to 65535 2500
Static Module
Module parameters
Diagnostic interrupt Activated/deactiv
ated
Deactivated
Behavior after channel
faults
Passivate the
entire
module/Passivate
the channel
Passivate the entire
module
HART_Gate Off/On/Can be
switched
Off
Interference frequency
suppression
50 Hz/60 Hz 50 Hz
Module
Evaluation of the
sensors
1oo1 evaluation,
1oo2 evaluation /
deactivated
1oo1 evaluation
Measuring range 4..20 mA /
0..20 mA
4...20 mA
F-wire break detection Activated/deactiv
ated
Activated
Smoothing 1, 4, 16, 64
conversion cycles
1 conversion cycle
Discrepancy time (ms) 0 to 30000 150
Tolerance window %,
absolute
0.2 to 20 2,5
Tolerance window %,
relative
0.2 to 20 2,5
Standard value MAX/MIN MIN
Static
Channel
HART
HART function On/off Off
HART repetitions 0 to 255 10
HART group diagnostics On/off Off
Static Channel