Analog modules
9.2 SM 336; AI 6 x 13 Bit
Fail-safe signal modules
184 Installation and Operating Manual, 01/2010, A5E00085586-10
9.2.2 Properties, front view, wiring diagram and block diagram
Order number
6ES7336-1HE00-0AB0
Properties
SM 336; AI 6 x 13Bit has the following properties:
● 6 analog inputs with electrical isolation between channels and the backplane bus
● Input ranges:
0 to 20 mA or 4 to 20 mA, 0 to 10 V in standard mode
4 to 20 mA in safety mode
● Short circuit-proof power supply of 2- or 4-wire transducers by the module
● External sensor supply possible
● Group fault display (SF)
● Safety mode display (SAFE)
● Sensor supply display (Vs)
● Programmable diagnostics functions
● Programmable diagnostic interrupt
● Supports operation in standard and safety mode
Use of inputs
You can use the inputs as follows:
● In standard mode
– All 6 channels for current measurement 0 to 20 mA or 4 to 20 mA, or
– Up to 4 channels for voltage measurement 0 to 10 V and the remaining 2 channels for
current measurement.
– Other combinations of current and voltage measurements; make allowances for
voltage measurement restrictions defined earlier.
● In safety mode
– All 6 channels for current measurements 4 to 20 mA.