Analog modules
9.3 SM 336; F-AI 6 x 0/4 ... 20 mA HART
Fail-safe signal modules
224 Installation and Operating Manual, 01/2010, A5E00085586-10
9.3.2 Properties, front view, wiring diagram and block diagram
Order number
6ES7336-4GE00-0AB0
Properties
SM 336; F-AI 6 x 0/4 ... 20 mA HART has the following properties:
6 analog inputs with electrical isolation between channels and the backplane bus
Input ranges:
0 to 20 mA
4 to 20 mA
Short circuit-proof power supply of 2- or 4-wire transducers by the module
External sensor supply possible
Group fault display (SF)
Safety mode display (SAFE)
Display for channel-specific fault (Fn)
Display for HART status (Hn)
(If you have activated HART communication for a channel and HART communication is
running, the green HART status display lights up.)
Programmable diagnostics functions
Programmable diagnostic interrupt
Supports operation in safety mode
SIL3/Cat.4/PLe can be achieved without safety protector
HART communication
Firmware update via
HW Config
I&M identification data
can be used with PROFINET IO
Use of inputs
You can use the inputs as follows:
Each of the 6 channels for current measurement
0 to 20 mA (without HART utilization)
4 to 20 mA (with/without HART utilization)
Functional range of HART communication: 1.17 to typ. 35 mA

Table of Contents

Other manuals for Siemens S7-300

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens S7-300 and is the answer not in the manual?

Siemens S7-300 Specifications

General IconGeneral
Protection ClassIP20
CPUCPU 312
CommunicationMPI, PROFIBUS, Ethernet
Power Supply24 V DC
ProgrammingSTEP 7 (TIA Portal)
Supply Voltage24 V DC
MountingDIN rail mounting
Operating Temperature0°C to 60°C
Relative Humidity10% to 95% (non-condensing)
MemoryDepends on CPU model (e.g., 64 KB to 4 MB)