EasyManua.ls Logo

Siemens S7-300 - 5.2 Wiring Fail-Safe Signal Modules

Siemens S7-300
356 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Wiring
5.2 Wiring Fail-Safe Signal Modules
Fail-safe signal modules
Installation and Operating Manual, 01/2010, A5E00085586-10
45
Power supply requirements for compliance with the NAMUR recommendation
Note
Always use power supply modules/units (230 V AC → 24 V DC) with integrated function for
power failure backup for the duration of at least 20 ms in accordance with NAMUR
recommendation NE 21, IEC 61131-2, and EN 298. Power supply components available
(examples):
S7-400
6ES7407-0KA01-0AA0 for 10 A
6ES7407-0KR00-0AA0 for 10 A
S7-300
6ES7307-1BA00-0AA0 for 2 A
6ES7307-1EA00-0AA0 for 5 A
6ES7307-1KA00-0AA0 for 10 A
These requirements, of course, also apply to power supply modules/units which are not
produced according to S7-300/400 installation technology.
5.2 Wiring Fail-Safe Signal Modules
Wiring similar to standard signal modules
The fail-safe signal modules belong to the S7-300 module family and are wired similar to any
standard signal module in the S7-300 or ET 200M system.
For further information on the wiring of fail-safe signal modules, refer to the
S7-300, CPU
31xC and CPU 31x: Installation
Operating Instructions.
The information in the module chapters includes special features to observe when wiring
specific F-SMs and the wiring diagrams for various applications with F-SMs.
WARNING
Note the following when assigning signals of fail-safe digital input modules:
Do not route signals within the same cable or light plastic-sheathed cable if their short
circuit could conceal a serious safety risk.
Only route signals within the same cable or light plastic-sheathed cable that are supplied
by different sensor supplies of this F-DI module.