Digital modules
8.6 SM 326; DO 10 x DC 24V/2A (6ES7326-2BF01-0AB0)
Fail-safe signal modules
148 Installation and Operating Manual, 01/2010, A5E00085586-10
Assignable parameters for applications 1, 3 and 5
Table 8- 19 Parameters of the SM 326; DO 10 x DC 24V/2A for applications 1, 3 and 5
Range of values
Parameters
Safety mode Standard mode
Type Effective
range
"Outputs" tab
Enable diagnostic
interrupt
Activated/deactivated Activated/deactivated Static Module
Mode
Safety mode
according to SIL 2
Safety mode
according to SIL 3
Standard mode Static Module
Monitoring time 10 ms to 10000 ms — Static Module
Disable light test Activated/deactivated Activated/deactivated Static Module
Reaction during
CPU STOP
—
Switch to fail-safe
value
Keep last valid
value
Static Module
Group diagnostics Activated/deactivated Activated/deactivated Static Channel
Switch to fail-safe
value "1"
— Activated/deactivated Static Channel
"Redundancy" tab
Redundancy none — Static Module