EasyManua.ls Logo

Siemens S7-300 - Page 220

Siemens S7-300
356 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Analog modules
9.2 SM 336; AI 6 x 13 Bit
Fail-safe signal modules
220 Installation and Operating Manual, 01/2010, A5E00085586-10
Technical data
Repeatability (in transient state at 25 °C, relative to
input range)
± 0,05 %
Operational limit (across the temperature range,
relative to input range)
Current
± 0,48 %
Voltage
± 0,48 %
Status, Interrupts, Diagnostics
Interrupts
Process interrupt
No
Diagnostic interrupt
Yes, assignable
Diagnostics functions Yes, assignable
Indication of safety-oriented operation
Green LED (SAFE)
Sensor supply monitoring
Green LED (Vs)
Group fault display
Red LED (SF)
Diagnostic information can be read out
Yes
Fail-safe values can be switched to Programmable in safety program
Sensor supply output
Number of outputs
1
Output voltage
Loaded
Minimum L+ (-1.5 V)
Output current
Rated value
1.0 A
Approved range
0 to 1.3 A
Short-circuit protection Yes, electronic
Electrical isolation in accordance with DIN VDE 0160
Between output Vs and the backplane bus
Yes
Between output and L+
No
Test voltage
600 VDC
Rated insulation voltage
75 VDC/60 VAC
Sensor selection data
Input range (rated values)/input resistance in standard mode
Voltage
0 to 10 V/59 kΩ
Current
0 mA to 20 mA
4 to 20 mA/107 Ω
Input range (rated values)/input resistance in safety mode
Current
4 to 20 mA/107 Ω
Permitted input voltage for voltage input
(destruction limit)
Max. 30 V continuous;
Max. 38 V for max. 1 s (pulse duty factor 1:20)
Permitted input current for current input
(destruction limit)
Max. 40 mA

Table of Contents