Analog modules
9.3 SM 336; F-AI 6 x 0/4 ... 20 mA HART
Fail-safe signal modules
244 Installation and Operating Manual, 01/2010, A5E00085586-10
Current measurement 0/4 to 20 mA with 2-wire and 4-wire transducer, transducer not redundant, for
application 4
Six process signals can be connected to two redundant modules in this interconnection
variant. One sensor is connected via one channel to the two modules for each process
signal. Sensor supply Vsn is provided by the module for 6 channels. The sensors can also
be connected to an external sensor supply (see Figure
External sensor supply, 2-wire
transducer for SM 336; F-AI 6 x 0/4 ... 20 mA HART
in chapter "Properties, front view, wiring
diagram and block diagram (Page 224)".
You can use interconnection
schemes E to H for this application.
60
$,[P$+$57
60
$,[P$+$57
/
0
9V
0
0
9V
0
0
9V
0
0
9V
0
0
9V
0
0
9V
0
0
/
0
9V
0
0
9V
0
0
9V
0
0
9V
0
0
9V
0
0
9V
0
0
/
0
3
/
0
&+
&+
&+
&+
&+
&+
&+
&+
&+
&+
&+
&+
ZLUH
WUDQVGXFHU
Figure 9-31 1oo1 evaluation, redundant F-SMs, single-channel transducer
For information about the Zener diodes, refer to chapter "Calculation of the residual supply
voltage at the transducer (Page 239)".
WARNING
To achieve SIL3/Cat.4/PLe using this wiring, you must use a suitably qualified sensor.
Note
You can supply the two F-SMs from two power supply units. If you use two power supply
units, the two grounds on the F-SMs will have to be connected with each other.