Configuration and parameter assignment
3.1 Configuring
Fail-safe signal modules
26 Installation and Operating Manual, 01/2010, A5E00085586-10
Configuring
The fail-safe signal modules are configured as usual, similar to standard modules, using
HW Config
.
Configuration in RUN (CiR)
The SM 326; DI 24 x DC 24 V (as of order no. 6ES7326-1BK01-0AB0) supports
configuration in run (CiR) when operated in standard mode (non-safety mode).
Additional information on CiR
For additional information on CiR, refer to:
In the
STEP 7
online help: "System changes in run using CiR"
In the
Safety Engineering in SIMATIC S7
system description
Enhanced availability in standard and safety mode
You can enhance availability by means of redundant operation of the F-SMs fail-safe signal
modules in standard mode (exception: SM 326; DO 8 x DC 24V/2A PM, SM 326; F-DO 10 x
DC 24V/2A PP and SM 336; F-AI 6 x 0/4 ... 20 mA HART).
Requirements:
STEP 7
V5.3 and higher, or
STEP 7
V5.2 or higher, plus optional software package
S7 H Systems
V5.2 or higher
In safety mode, you can operate the F-SMs redundantly in S7 F/FH Systems F-systems
(with the exception of SM 326; DO 8 x DC 24V/2A PM).
Requirements:
STEP 7
V5.3 and higher, or
STEP 7
V5.2 or higher, plus optional software package
S7 H Systems
V5.2 or higher
S7 F Systems
optional software package
F Configuration Pack
V5.3 Service Pack 1 or higher
for SM 326; DI 24 x DC 24V, as of order no. 6ES7326-1BK01-0AB0:
F Configuration
Pack
V5.3 Service Pack 3 or higher
for SM 336; F-AI 6 x 0/4 20 mA HART:
F Configuration Pack
V5.5 Service Pack 4 or
higher
for SM 326; F-DO 10 x DC 24V/2A PP:
F Configuration Pack
V5.5 Service Pack 6 or
higher
You can download the
F Configuration Packs
from the Internet
(http://support.automation.siemens.com/WW/view/en/15208817
).
You enhance availability of the modules by assigning the corresponding parameters in the
"Redundancy" tab of the object properties dialog for the modules.