Analog modules
9.3 SM 336; F-AI 6 x 0/4 ... 20 mA HART
Fail-safe signal modules
280 Installation and Operating Manual, 01/2010, A5E00085586-10
HART commands and parameters
You can use
SIMATIC PDM
to set the parameters of the HART field devices via HART
commands and read these out via HART replies. The HART commands and their
parameters are divided into three groups with the following properties:
universal
generally usable
device specific
Universal command must be supported by all manufacturers of HART field devices; it is
recommended that generally useable commands be supported. In addition there are device-
specific commands, which only apply to the specific field device.
Examples of HART parameters
The following table shows HART parameters of various groups:
Table 9- 27 Examples of HART parameters
Parameter group Parameters of the HART field device
universal Measuring and manipulated variable (primary
variable), manufacturer's name, process or
actuator tags, other measured and manipulated
values
generally usable Measuring range, filter time, interrupt parameters
(message, interrupt and warning limits), output
range
device specific special diagnostic information
See also
HART communication records (Page 289)