EasyManua.ls Logo

Siemens S7-300 - Page 93

Siemens S7-300
356 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Digital modules
8.3 SM 326; DI 24 x DC 24V
Fail-safe signal modules
Installation and Operating Manual, 01/2010, A5E00085586-10
93
WARNING
To achieve SIL3/Cat.4/PLe using this wiring, you must use a suitably qualified sensor.
Assignable parameters for application 5
Table 8- 6 Parameters for application 5 of SM 326; DI 24 x DC 24V
Parameters Range of values in safety mode Type Effective range
"Parameters" tab
Mode of operation Safety mode Static Module
F parameter:
F monitoring time 10 ms to 10000 ms Static Module
Module parameters:
Diagnostic interrupt Activated/deactivated Static Module
Module parameters for a power supply group:
Internal sensor supply
of the module
Activated/deactivated Static Power supply group
Short-circuit test activated/deactivated * (only if "Sensor
Supply via Module" is activated)
Static Power supply group
For single channels or channel pairs:
activated activated/deactivated Static Channel pair
Evaluation of the
sensors
1oo2 evaluation Static Channel pair
Type of sensor
interconnection
Two-channel, equivalent
Two-channel, nonequivalent
Single-channel
Static Channel pair
Discrepancy behavior (only two-channel)
"Provide last valid value"
Provide 0 value
Static Channel pair
Discrepancy time 10 ms to 30000 ms (only for two-
channel)
Static Channel pair
* Vs does not clock, if the short-circuit test is deactivated.

Table of Contents

Other manuals for Siemens S7-300

Related product manuals