Technical specifications
7.2 SCALANCE X106-1
SCALANCE X-100
46 Operating Instructions, 12/2016, A2B00060666-08
0 to 100 m
• Max. 100 m IE FC TP Standard Cable with IE FC RJ45 Plug 180
• Max. 90 m IE FC TP Standard Cable + 10 m TP Cord via IE FC RJ45 Outlet
Multimode glass FO cable, cable cross sections 62.5/125 μm and 50/125 μm
Permitted cable length (glass FO
cable)
• 62.5/125 μm
• 50/125 μm
• 0 to 4000 m
• 0 to 5000 m
Attenuation ≤ 1 dB/km at 1300 nm
1200 MHz x km at 1300 nm
6 dB max. permitted FO cable attenuation with
Power supply Voltage range 18 to 32 VDC Safe Extra Low Voltage
Signaling contact
2-pin plug-in terminal block
Overvoltage protection at input
PTC resettable fuse (0.6 A / 60 V)
Permitted ambient conditions
Ambient temperature
During storage -40 °C to +80 °C
During transportation -40 °C to +80 °C
Relative humidity During operation ≤ 95 % no condensation
Operating altitude During operation ≤ 2,000 m above sea level at max. 56 °C
ambient temperature
≤ 3,000 m above sea level at max. 50 °C
Design, dimensions and weight
MTBF (EN/IEC 61709, 40 °C)
Housing material
Die cast aluminum, powder coated
Front cover Polyphenylene ether + polystyrene