EasyManua.ls Logo

Siemens SCALANCE X-100 - Page 58

Siemens SCALANCE X-100
78 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical specifications
7.7 SCALANCE X124
SCALANCE X-100
58 Operating Instructions, 12/2016, A2B00060666-08
Technical specifications
CoS acc. to IEEE 802.1Q
Yes
QoS priority queues
4
Note
The number of SCALANCE X Industrial Ethernet switches connected in a line influences the
frame delay time.
When a frame passes th
rough devices of the SCALANCE X-
100 product line, it is delayed by
the store and forward function of the switch
with a 64 byte frame length by approx. 10 microseconds (at 100 Mbps)
with a 1500 byte frame length by approx. 130 microseconds (at 100 Mbps)
Thi
s means that the more devices of the SCALANCE X-100 product line, the frame passes
through, the longer the frame delay.
Note
Temperature code for c-UL-us for hazardous locations, FM and ATEX Zone 2
You will find the temperature code "T.." or the maximum ambient temperature "Ta: .." on the
type plate.