EasyManua.ls Logo

Siemens SENTRON PAC3120 - Device Labeling

Siemens SENTRON PAC3120
160 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical data
10.1 Technical data
104
PAC3120 and PAC3220
Equipment Manual, 10/2019, L1V30425208F-01
Ambient conditions
The device is suitable for switch panel mounting in accordance with IEC 61554. The device
may only be operated within enclosed dry rooms.
Ambient conditions
Temperature range Ambient temperature
during operation
25 +55 °C (K55)
Ambient temperature
during transportation and storage
25 +70 °C
Relative humidity
< 75 % RH
Installation altitude above sea level
Max. 2000 m
Pollution degree
2
Environmental tests
EN 60068-2-27
EN 60068-2-6
EN 60068-3-3
Relative humidity in relation to ambient temperature
The maximum relative humidity is 80 % at temperatures up to 31 °C, decreasing linearly
down to 50 % relative humidity at 40 °C.