Commissioning
5.6 Checking the displayed measured values
60
PAC3120 and PAC3220
Equipment Manual, 10/2019, L1V30425208F-01
5.6 Checking the displayed measured values
Correct connection type
With the help of the table "Display of measured variables depending on the connection type",
check whether the measured variables are displayed in accordance with the connection type
executed. Any deviation indicates a wiring fault or configuration error.