PAC3120 and PAC3220
Equipment Manual, 10/2019, L1V30425208F-01
35
Mounting location
The devices are intended for installation in permanently installed switching panels within
closed rooms.
Only operate the device in a secure location.
Failure to heed this warning may cause death, serious personal injury, or equipment
damage.
The power monitoring device must always be operated in a lockable control cabinet or a
lockable room. Ensure that only qualified personnel have access to this cabinet or room.
Conductive panels and doors on control cabinets must be grounded. The doors of the control
cabinet must be connected to the control cabinet using a grounding cable.
Mounting position
The device must be installed vertically.
Figure 3-1 Mounting position