Parameter assignment
7.2 Parameterizing via the operator interface
86
PAC3120 and PAC3220
Equipment Manual, 10/2019, L1V30425208F-01
7.2.8.3 Resetting
Selection
Range
Factory setting
CLEAR MIN/MAX VALUES Resets all minimum and maximum values to the
instantaneous value.
Yes: active
No: not active
No
RESET COUNTERS Resets the following counters to zero (0):
Energy counters
Active energy
Reactive energy
Apparent energy
Operating hours counter
Yes: active
No: not active
No
UNIV. COUNTER RESET Resets the configurable universal counter to zero
(0).
Yes: active
No: not active
No
FACTORY DEFAULTS All device settings and measured values except
the communication parameters and energy sec-
ondary values are reset to the as-delivered condi-
tion.
Yes: active
No: not active
No
COMMUNICATION
PARAMETERS
All communication settings are reset to the as-
delivered condition.
Yes: active
No: not active
No
EXECUTE Confirmation of the reset
Note
The reset must be confirmed by selecting the "Execute" field. Otherwise the device reset is
not executed.