EasyManua.ls Logo

Siemens SENTRON PAC3120 - Page 49

Siemens SENTRON PAC3120
160 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Connection
4.3 Connection examples
PAC3120 and PAC3220
Equipment Manual, 10/2019, L1V30425208F-01
47
2. 3-phase measurement, 4 conductors, unbalanced load, with voltage transformer, with
3 current transformers
Connection type 3P4W
* The fuses are only used for cable protection.
All commercially available miniature circuit breakers up to 20 A (C) can be used.
**
Connection of supply voltage
Figure 4-4 Connection type 3P4W, with voltage transformer, with three current transformers
3. 3-phase measurement, 4 conductors, unbalanced load, without voltage transformer, with
1 current transformer
Connection type 3P4WB
* The fuses are only used for cable protection.
All commercially available miniature circuit breakers up to 20 A (C) can be used.
**
Connection of supply voltage
Figure 4-5 Connection type 3P4WB, without voltage transformer, with 1 current transformer

Table of Contents

Related product manuals