Technical data
10.1 Technical data
96
PAC3120 and PAC3220
Equipment Manual, 10/2019, L1V30425208F-01
Measuring inputs for voltage
Measuring inputs for voltage
Measurable voltage Rated voltage 57.7/100 … 400/690 V (IEC)
57.7/100 … 347/600 V (UL)
Min. measuring voltage U
L-N
Max. measuring voltage U
L-N
480 V (IEC)
416 V (UL)
Zero point suppression level
Measuring category
(acc. to IEC/UL 61010-2-030)
Impulse withstand voltage
Max. power consumption per phase
Measuring inputs for current
Only for connection to AC power systems via external current transformers.
Measuring inputs for current
Input current I
E
Measuring range of current
10 … 120 % of rated current
Measuring range for power and energy measurement
1 … 120 % of rated current
Surge withstand capability
Max. permissible continuous current
Max. power consumption per phase
Zero point suppression level
0 … 10 % of rated current