Bit 15 14 13 12 11 10 9 8
Not used Not used Not used Not used Hours
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
Bit 7 6 5 4 3 2 1 0
Not used Not used Not used Minutes
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
Format 5-bit unsigned integer
Unit h
Range 0 to 23
Format 6-bit unsigned integer
Unit min
Range 0 to 59
Time in Month and Date
(Address 304, 314, …., 494) This register contains the time in month and date.
Bit 15 14 13 12 11 10 9 8
Not used Not used Not used Not used Not used Month
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
Bit 7 6 5 4 3 2 1 0
Not used Not used Not used Not used Date
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
Format 5-bit unsigned integer
Unit Date
Range 1 to 31
Format 4-bit unsigned integer
Unit Month
Range 1 to 12
Time in Year
(Address 305, 315, …., 495) This register contains the time in years.
Bit
15 14 13 12 11 10 9 8
Not used Not used Not used Not used Not used Not used Not used Not used
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
Bit 7 6 5 4 3 2 1 0
Not used Year
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
Format 7-bit unsigned integer
Unit Year
Range 12 to 99
For example, if Modbus value is:
12 = Year 2012
99 = Year 2099
Modbus Registers
B.7 Register-Type Data - Events
SICAM, Feeder Condition Monitor, Manual 151
E50417-H8940-C580-A4, Edition 03.2019