EasyManua.ls Logo

Siemens SICAM - A.3 Editing Device Settings

Siemens SICAM
174 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Editing the Device Settings
This chapter describes with an example how to edit and set the device parameters.
To edit the phase-current threshold value settings, proceed as follows:
²
On the default menu, select Menu.
The Menu appears.
²
Navigate to the Fault Parameters menu and press OK.
The Phase-Fault Detection I>> menu with the different phase-fault parameters appears.
²
Navigate to Phase-Fault Detection I>> and press OK.
The Saved I >> menu appears.
²
In the Saved I >> menu, press Edit>.
The New I>> menu appears.
²
In the New I >> menu, press the up arrow or the down arrow to set the New I>> value within the desired
range.
²
Press Save> to save the new Phase-Fault Detection I>> value.
i
i
NOTE
To navigate from one value to another value, use the left arrow and right arrow. For entering values, for
example, from 0 A to 2500 A, press the up arrow or the down arrow.
²
Press Esc if you want to cancel the edit mode and to return to the display mode. All the saved values are
discarded.
[dw_sfcmeditparaset, 1, en_US]
Figure A-3
Editing Phase-Protection Settings
A.3
Parameterization
A.3 Editing the Device Settings
SICAM, Feeder Condition Monitor, Manual 91
E50417-H8940-C580-A4, Edition 03.2019

Table of Contents

Related product manuals