Register-Type Data – Trailing Pointers
(Address 101 to 282) This register stores the minimum value and the maximum value of I
1
, I
2
, I
3
, I
N
, P, Q, and
the S values for the respective phases at regular intervals. The interval ranges are 15 minutes, 30 minutes, 45
minutes, 60 minutes, 24 hours, 1 month, and 1 year.
Table B-16 Trailing Pointers
Parame-
ters
15 Minutes 30 Minutes 45 Minutes 60 Minutes 24 Hours 1 Month 1 Year
Min
value
Max
value
Min
value
Max
value
Min
value
Max
value
Min
value
Max
value
Min
value
Max
value
Min
value
Max
value
Min
value
Max
value
I
1
101 114 127 140 153 166 179 192 205 218 231 244 257 270
I
2
102 115 128 141 154 167 180 193 206 219 232 245 258 271
I
3
103 116 129 142 155 168 181 194 207 220 233 246 259 272
I
N
104 117 130 143 156 169 182 195 208 221 234 247 260 273
P
1
105 118 131 144 157 170 183 196 209 222 235 248 261 274
P
2
106 119 132 145 158 171 184 197 210 223 236 249 262 275
P
3
107 120 133 146 159 172 185 198 211 224 237 250 263 276
Q
1
108 121 134 147 160 173 186 199 212 225 238 251 264 277
Q
2
109 122 135 148 161 174 187 200 213 226 239 252 265 278
Q
3
110 123 136 149 162 175 188 201 214 227 240 253 266 279
S
1
111 124 137 150 163 176 189 202 215 228 241 254 267 280
S
2
112 125 138 151 164 177 190 203 216 229 242 255 268 281
S
3
113 126 139 152 165 178 191 204 217 230 243 256 269 282
Phase Current I
1
(Address, see Table B-16) This register contains the minimum values and the maximum values of the phase
current I
1
measured every 15/30/45/60 minutes, 24 hours, 1 month, and 1 year respectively.
Bit
15 14 13 12 11 10 9 8
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
Bit 7 6 5 4 3 2 1 0
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
Format 16-bit unsigned integer
Unit A
Range 0 to 9999
Phase Current I
2
(Address, see Table B-16) This register contains the minimum values and the maximum values of the phase
current I
2
measured every 15/30/45/60 minutes, 24 hours, 1 month, and 1 year respectively.
Refer to Phase Current I
1
, Page 153.
Phase Current I
3
(Address, see Table B-16) This register contains the minimum values and the maximum values of the phase
current I
3
measured every 15/30/45/60 minutes, 24 hours, 1 month, and 1 year respectively.
Refer toPhase Current I
1
, Page 153.
B.8
Modbus Registers
B.8 Register-Type Data – Trailing Pointers
SICAM, Feeder Condition Monitor, Manual 153
E50417-H8940-C580-A4, Edition 03.2019