Register-Type Data – Holding Registers
Modbus Frame Configuration
(Address 1) This register defines the Modbus frame configuration.
Bit 15 14 13 12 11 10 9 8
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
Bit 7 6 5 4 3 2 1 0
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
Format 16-bit unsigned integer
No Parity 0
Even Parity 1
Odd Parity 2
Default 0
Modbus Baud Rate
(Address 2) This register defines the Modbus baud rate.
Bit 15 14 13 12 11 10 9 8
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
Bit 7 6 5 4 3 2 1 0
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
Format 16-bit unsigned integer
Range 0 to 6
Baud rate (bps) 0
1
2
3
4
5
6
2400
4800
9600
19200
38400
57600
115200
Default 6 115200 bps
Modbus ID
(Address 4) This register defines the Modbus ID.
Bit
15 14 13 12 11 10 9 8
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
Bit 7 6 5 4 3 2 1 0
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
Format 16-bit unsigned integer
Range 1 to 247
Default 247
Date and Time
(Address 5 to 8) The format used for date and time complies with EN60870-5- 4:1993. It consists of 4 succes-
sive registers for writing in one request. It uses the function code 16.
(Address 5)
B.4
Modbus Registers
B.4 Register-Type Data – Holding Registers