Register-Type Data – Input Registers
Phase Current I
1
(Address 1000) This register contains the phase current I
1
.
Bit 15 14 13 12 11 10 9 8
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
Bit 7 6 5 4 3 2 1 0
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
Format 16-bit unsigned integer
Unit A
Range 0 to 65535
Phase Current I
2
(Address 1001) This register contains the phase current I
2
.
Refer to Phase Current I
1
, Page 131.
Phase Current I
3
(Address 1002) This register contains the phase current I
3
.
Refer to Phase Current I
1
, Page 131.
Ground Current I
N
(Address 1003) This register contains the actual ground-current value I
N
.
Bit
15 14 13 12 11 10 9 8
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
Bit 7 6 5 4 3 2 1 0
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
Format 16-bit unsigned integer
Unit A for solid connection
1/100 A for isolated/resonant systems
Range 0 to 65535
For example, if Modbus value is:
40 = 0.4 A
600 = 6 A
Refer to Phase Current I
1
, Page 131.
Voltage V
12
(Address 1004) This register contains the actual voltage V
12
.
Bit
15 14 13 12 11 10 9 8
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
Bit 7 6 5 4 3 2 1 0
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
B.5
Modbus Registers
B.5 Register-Type Data – Input Registers
SICAM, Feeder Condition Monitor, Manual 131
E50417-H8940-C580-A4, Edition 03.2019