EasyManua.ls Logo

Siemens SICAM - 7.1 Connection Types; Fault Passage Indicator; Ground-Fault Indicator; Fault Detector

Siemens SICAM
174 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Connection Diagrams
This chapter describes the various possibilities to connect the device to the medium-voltage system.
Fault Passage Indicator
The device can be used as a dedicated Fault Passage Indicator (FPI) by using only the 3 current inputs. No
directional fault information is provided in this scheme.
[dw_sfcm-sfpi, 2, en_US]
Figure 7-1 SICAM FCM as Fault Passage Indicator
i
i
NOTE
In this connection scheme, the accuracy of ground-current measurements cannot be guaranteed for
isolated/resonant ground connection.
Ground-Fault Indicator
The device can be used as a dedicated ground-fault indicator by using the ground-current sensor. The
following scheme shows how the device works as a non-directional ground-fault indicator (50 G).
[dw_sfcm_grdfltindi, 2, en_US]
Figure 7-2 SICAM FCM as Ground-Fault Indicator
Fault Detector
The device can be used as a fault detector by providing fault information with directional information. This
requires an additional low-power voltage transformer of 3.25/√3 V or 100/√3 V sensors in the medium-voltage
system or a direct connection to 230 V or when it is connected in the VDS.
For more information about VDS, see chapter 4.1.32 Voltage Measurement via Integrated Voltage-Detecting
Systems.
7.1
Connection Diagrams
7.1 Connection Diagrams
70 SICAM, Feeder Condition Monitor, Manual
E50417-H8940-C580-A4, Edition 03.2019

Table of Contents

Related product manuals